Generators, diesel, 6 to 15 kVA, single/three phase

   

Code

Description

Ind. price

Ship. weight

Ship. Vol.

EGENDIGE006T

GENERATOR, 6kVA, 240/400V tri. diesel, 1500rpm

CHF5’420

450kg

1.42 x0.75 x1.12m

total vol.: 1.2m³

EGENDIGE007T

GENERATOR, 7.5kVA, 240/400V tri. diesel, 1500rpm

CHF5’920

480kg

1.72 x0.70 x1.30m

total vol.: 1.57m³

EGENDIGE012T

GENERATOR, 12kVA, 240/400V tri. diesel, 1500rpm

CHF6’510

500kg

1.72 x0.70 x1.30m

total vol.: 1.57m³

EGENDIGE015T

GENERATOR, 15kVA,  240/400V tri. diesel, 1500rpm

CHF7’050

500kg

1.72 x0.70 x1.30m

total vol.: 1.57m³

Cold chain: No               Dangerous: Yes-if with battery                    Regulated: Yes-IATA if with battery

General information

q     Standard generators for electrical power supply where the mains supply is not accessible/reliable.

q     These generators come standard with 3 phase. On request they can be supplied with single phase wiring set up. This can be necessary for a building where the original circuit is single phase.

q     Different engines are presented, they are the recommended standards. Other brands can also be the preferred choice according to the regional availability, and standards already in place. Supply of spare parts and technical support for maintenance and repair are major issues in the long run.

q     The power of the standard engines is adapted for use at 150m ASL altitude and 30°C ambient. If the conditions of use are more severe (higher altitude and/or hotter temperature), specify on your order the altitude and the ambient temperature. See technical pages …

q       Technical knowledge required to calculate the total power needs and to choose the generator accordingly.

q       See technical advises for generator set up and pumping set up in chapter “W” technical pages.

q     A circuit inverser switch (Main/Off/Generator) is included in the set to adapt the generator onto an existing circuit already supplied from the mains.

q     Noise reduction canopy is recommended in all cases. Different levels of noise reduction are available at different cost. Industrial type (standard) is not recommended in residential area. Above prices include standard noise reduction canopy.

q     Should always be supplied with a first maintenance set of:

-       Air filter (5), Fuel filter (10), Oil filter (10).

q     Trailer mounted option. 2 types available: “On site trailer” and “Road trailer”. The site trailer is limited to 40 kph maximum speed, and does not have lights and equipment to go on road. Not included in above prices (CHF1200 for site trailer, CHF4000 for road trailer, up to 20kVA).

Specifications

Diesel engine, 4 stroke, without turbo charger, direct injection, water cooled, 1500rpm, electric start.

Generator power                               6kVA                   7.5kVA                12kVA                 15kVA

Lombardini engine                             LDW602              LDW903              LDW1204            LDW1503

Lister Petter engine                                                        LPW2                  LPW3                  LPW4

Deutz engine                                                                  F3M1800             F4M1008            

Typical consumption at 100%            1.9L/hour             2.9L/hour              4.2L/hour             5.2L/hour

Alternator, self regulating, self excited, 240/400V 3 phase, 10% overload capacity for 1.5hour. Insulation class H. Flanged coupled with engine.

Control panel. Mounted in the canopy. Accessible from outside. Includes:

Volt meter (3). Ampere meter (3). Frequency meter (1). Hour counter. Water temperature gauge. Oil pressure gauge, charge warning light. Starter key (+1spare key). Emergency stop push on switch. Receptacle 3 x 220V Euro type, minimum. 1 circuit breaker per receptacle. Main/Off/Generator switch. Differential circuit breaker rated 300mA.

Automatic shut off for oil pressure failure, water temperature failure, charging failure.

Generator set mounted on skid with anti vibration mounts, with steel plate complete canopy. Forced ventilation. Fuel tank integrated in skid, of 100L minimum. Canopy and all equipment to be weather proof, with locking doors, painted in white. 1 or 2 lifting points. Earth connection.

Noise reduction         Industrial (standard):       78db at 7m

                                 Residential level 1:          63db at 7m

                                 Residential level 2:          58db at 7m

Operator manual, repair manual, spare parts manual, for the alternator and the engine, in English. Earth rod with 4m cable. 10 oil filter elements. 10 fuel filter elements. 5 air filter elements.